VII.C: 110kV Current transformer
Standard: IEC – 60044 – 1;
Technical parameters:
Single phase, outdoor type.
Rated voltage: 123 kV
Rated frequency: 50Hz
Short - time withstand current: 25kA/3s
Making current: 63kA.
Ratio: 200-400-600-800/1A.
Number of secondary windings: 4
Accuracy & burden:
Core 1: 0.5-30 VA (for measurement)
Core 2, 3: 0.5-30 VA (for Protection)
Core 4: 5P20 - 30 VA (for busbar protection)
Insulation:
Oil immersed
Rated lightning impulse-withstand voltage: 550kV
Rated power frequency-withstand voltage:
- Primary: 230kV
- Secondary: 3kV
Limits of temperature rise of windings: 60 oC
Limits of temperature rise of oil: 55 oC
Minimum creepage distance: 25mm/kV
Accessories:
+ Oil level indicator.
+ Oil valve for draining.
+ Zinc galvanized Supporting structure, bidder must provide shop drawing for manufacturing the steel structure.
+ Terminal for conductor 185 mm2, earthing terminal
+ Document for installation, operation, maintenance, and test report.
Special note: Bidder provides following document for bid evaluation.
- Type test certificate (as per IEC 60044-1).
- List of clients.
- Operating certificate of clients.
If you can't find more Buying Leads related to your items, why not post your Products instead?
It will let your potential buyers to contact you directly.
Browse: Manufacturer Directory Premium Suppliers Site Map
About EC21 Contact Us Terms & Conditions Report Item Online Trading Risks Product Listing Policy
Copyright (c)1997-2026 EC21 Inc. All Rights Reserved. EC21 in KoreanChinese
Business Registry Number: 120-86-03931 | Mall order sales Registration Number: 강남-5838