Sign In | Join Free | Messenger | Inquiry Basket () | Help

Buy Current Transformer

Buying Lead Info
Date Posted : 2008-07-07
Valid until : 2008-07-13
Inquiry Now

VII.C: 110kV Current transformer
Standard: IEC – 60044 – 1;
Technical parameters:
        Single phase, outdoor type.
        Rated voltage: 123 kV
        Rated frequency: 50Hz
Short - time withstand current: 25kA/3s
Making current: 63kA.
               Ratio: 200-400-600-800/1A.
        Number of secondary windings: 4
Accuracy & burden:
        Core 1: 0.5-30 VA             (for measurement)
                Core 2, 3: 0.5-30 VA         (for Protection)
        Core 4: 5P20 - 30 VA        (for busbar protection)

Insulation:
        Oil immersed
        Rated lightning impulse-withstand voltage: 550kV
        Rated power frequency-withstand voltage:
- Primary: 230kV
- Secondary: 3kV
        Limits of temperature rise of windings: 60 oC
        Limits of temperature rise of oil: 55 oC
        Minimum creepage distance: 25mm/kV

Accessories:
        + Oil level indicator.
        + Oil valve for draining.
+ Zinc galvanized Supporting structure, bidder must provide shop drawing for manufacturing the steel structure.
+ Terminal for conductor 185 mm2, earthing terminal
        + Document for installation, operation, maintenance, and test report.

Special note: Bidder provides following document for bid evaluation.
- Type test certificate (as per IEC 60044-1).
- List of clients.
- Operating certificate of clients.





If you can’t find more Buying Leads related to your items, why not post your Selling Leads and Products instead? It will let your potential buyers to contact you directly.